E-mail
139@qq.com
-
Phone
15956085358
-
Address
Tianchang
Anhui Yaokang Automation Instrument Co., Ltd
139@qq.com
15956085358
Tianchang
1、 Main technical parameters**
1. * * Measurement range**
-Conventional range: 0-25% O ₂ (some models can be extended to 0.05% -20.6% or 0.1% -100%).
-Accuracy level: Level 1 (basic error<± 3% F.S), and the accuracy of some secondary instruments can reach ± 0.2%.
2. * * Environmental adaptability**
-* * Smoke temperature * *:
-Low temperature type (such as ZO-4): ≤ 600 ℃ or 800 ℃ (slightly different definitions from different manufacturers);
-High temperature type (such as ZO-5): 600-1200 ℃ or 800-1300 ℃.
-Working pressure range: -100kPa to+100kPa (some models support ± 50kPa).
3. * * Output and Communication**
-Output signal: 4-20mA (mainstream) or 0-10mA, partially supports RS-485/RS-232 communication.
-Load capacity: Load resistance ≤ 600 Ω when outputting 4-20mA, ≤ 1.2k Ω when outputting 0-10mA.
4. * * Power consumption and response time**
-Power consumption of transmitter: about 8W, average power consumption of heating furnace is 50W (some high-temperature models reach 120W).
-Response time: 90% response takes about 3 seconds.
5. * * Structure and Installation**
-Probe material: High temperature resistant stainless steel (such as 304, 316L) or ceramic, with a protection level of IP65/IP66.
-Insertion depth: 400-1400mm, supports flange installation (common for DN50).
6. * * Other parameters**
-Background potential correction range: -20mV to+20mV.
-Service life: Zirconia tubes are guaranteed to last for six months to one year, with a main lifespan of up to eight years (depending on the type of fuel, such as shorter lifespan under coal-fired conditions).
2、 Application scenarios**
1. * * Industrial combustion equipment**
-Used for monitoring the oxygen content of flue gas in boilers, kilns, heating furnaces and other equipment, achieving low oxygen combustion control, reducing energy consumption and pollutant emissions.
2. * * Power industry**
-Thermal power plants, waste to energy plants, biomass power plants, etc. monitor the combustion efficiency of coal-fired and gas-fired boilers. For example, the ZO-12B model is designed specifically for power plants and is suitable for temperatures ranging from 0 to 700 ℃.
3. * * Chemical and Metallurgical Industry**
-High temperature furnace flue gas monitoring in the petrochemical and steel metallurgy industries supports high temperature (≤ 1300 ℃) and corrosive environments.
4. Environmental protection field**
-Control the oxygen content in the flue gas of garbage incinerators and hazardous waste treatment equipment to ensure compliance with emission standards.
5. * * Other industries**
-Optimization of combustion equipment in industries such as glass manufacturing, pharmaceuticals, and textiles, suitable for various fuel types such as natural gas and fuel oil.
3、 Selection and installation precautions**
1. * * Selection points**
-Select probe materials based on flue gas temperature, pressure, and medium corrosiveness (such as 316L, which has stronger corrosion resistance).
-Determine the installation method (direct insertion, bypass) and the type of secondary instrument (panel mounted, wall mounted, or explosion-proof).
2. * * Installation requirements**
-The probe should be tilted and inserted into the flue to avoid the accumulation of condensed water; The flange connection needs to be sealed, and the signal line needs to be shielded.
-The inner diameter of the bypass flue is ≥ 100mm, and sampling holes are set up to ensure representativeness.