E-mail
2067886464@qq.com
-
Phone
13002785510
-
Address
Hengyi Baolian, Kuiwen District, Weifang City, Shandong Province
Shandong BenQ Environmental Protection Equipment Co., Ltd
2067886464@qq.com
13002785510
Hengyi Baolian, Kuiwen District, Weifang City, Shandong Province
The PAC dosing device meets various technical requirements of the sewage treatment plant. The entire equipment includes a mixing tank, agitator, dosing pump, level gauge, solenoid valve, pneumatic ball valve, globe valve, Y-shaped filter, safety valve, pulse damper, pressure gauge, back pressure valve, etc. The PAC dosing device is also equipped with a PLC automation control system for controlling the automatic operation of the dosing system.
Working principle of PAC dosing deviceAt the same time as measuring water flow, PAC is added to the water to achieve automated coagulation process. The process is as follows:
1. Measuring water flow rate: The PAC dosing device controls the dosage of PAC by measuring the water flow rate. Generally, flow measurement equipment such as electromagnetic flow meters or turbine meters are accepted, which can accurately measure the flow rate of water.
2. Medication control: Based on the measured water flow rate and the set PAC dosing ratio, the speed of the PAC dosing pump is automatically controlled to achieve accurate and clear dosing control.
3. Stirring and mixing: After adding PAC, a specific stirring and mixing process is required to achieve sufficient dispersion and mixing of PAC, so that it can fully contact impurities in the water and complete the coagulation effect. We generally accept mixing equipment such as direct mixers or static mixers.
4. Precipitation removal: After coagulation reaction, impurities in the water will precipitate to the lower part of the water and need to be removed by sedimentation tanks and other equipment.
Installation and commissioning of PAC dosing device:
1. Our company is responsible for the installation guidance of the entire PAC dosing device, as well as the debugging and trial operation of the equipment. We are also responsible for the quality and normal operation of the equipment during the warranty period.

2. Our company will send personnel to the site within 3 days after receiving the owner's request or phone call.Working principle of PAC dosing device
3. Before the installation of the equipment begins, our company provides corresponding installation requirements and drawings.
4. After the installation and debugging are completed, the owner needs to conduct a comprehensive written evaluation of the technical level, moral character, and work attitude of our company's technical personnel, and sign and stamp it.
Tips for blocking PAC dosing device:
1. Dissolving PAC is still better done with aeration mixing, but the dispensing process should be slower. If the owner's medication is already prepared, only slightly mix it when using.
2. A storage tank of about 1.5 square meters is used for aeration and mixing. A self-priming pump is installed below the tank, followed by a reflux system. A 1-inch PVC pipe is used. The concentration of the medicine is about 10% (rumored to hydrolyze if it is too low), and 3-5 kg of medication is added every hour without filtration. It is pumped into the coagulation tank with mud and water.
3. PAC has a short shelf life, and one month is not acceptable. This is the root cause and has little to do with pipeline reflux. Advocate for purchasing PAC agents with longer shelf life.
The PAC dosing device undergoes factory inspection and functional testing before leaving the factory. The manufacturing, electrical connections, and functions of the equipment are comprehensively tested as required, and the test results are attached to the product quality certificate.

Common models of PAC dosing devices
The selection of PAC dosing device needs to be evaluated based on factors such as actual business needs and flow range. The commonly used PAC dosing device models on the market currently include:
TCL-PAC-AUTO: Suitable for a flow range of 2-200m3/h, accepts electromagnetic flow meters to measure water flow, with high accuracy and stability.
EPC-11: Suitable for a flow range of 5-200m3/h, it is controlled by a microcomputer and has functions such as automatic adjustment and alarm. It is easy to operate and use.
PAC-JYQ: Suitable for a flow range of 5-150m3/h, it accepts measurement of water flow using a turbine flowmeter and has the advantages of being compact, flexible, energy-saving, and environmentally friendly.
Maintenance of PAC dosing device
1. Regular inspection: Regularly check the operation status of equipment, including the operation of power supply, conveying system, chemical dosing device, etc., and promptly detect and solve faults.
2. Cleaning and replacement: Regularly clean the equipment to remove dirt and sediment inside, ensuring that the equipment is unobstructed. At the same time, according to the usage of the equipment, regularly replace accessories such as chemicals and filters.
3. Maintenance: Regularly inspect and maintain various components of the equipment, including power lines, transmission devices, valves, etc., to ensure the normal operation and safety of the equipment.
4. Pay attention to safety: During maintenance, pay attention to relevant safety precautions of the equipment, such as power outage operations, grounding protection, etc., to ensure the safety of personnel and equipment.