Product Name: |
Seven in one air quality detector |
|
Product model: |
MAQ01020406070914-S-P2 |
|
edition: |
V1.0 |
|
Developed by: |
He Genwen |
|
Reviewer: |
Yuan Chao |
The seven in one air quality detector is a cost-effective digital signal output sensor product that uses RS485 output mode and integrates CO2, formaldehyde TVOC、 Integrated laser dust PM2.5/PM10 particle, temperature, and humidity sensors. It can perform real-time comprehensive detection of the environment, has good stability, and is very convenient for customers to use.
Hotel room air quality monitoring
● Fresh air exchange system
Air purifier, air conditioner
Air quality monitoring equipment
Kitchen and bathroom ventilation control system
● Smart home devices
Simultaneously output CO2, formaldehyde TVOC、PM2.5、PM10、 Seven sets of temperature and humidity data
High sensitivity and stable data
RS485 output
Temperature resolution 0.1 ℃, humidity resolution 0.1% RH
Up to 0.5 seconds to output seven sets of sensor monitoring data through RS485 signal output
|
Category |
Measurement resolution |
Measurement range |
Measurement accuracy |
|
CO2 |
1ppm |
400ppm~5000ppm |
± 50ppm+5% reading |
|
formaldehyde |
1ug/m3 |
0ug~1000ug/m³ |
±25% |
|
TVOC |
1ug/m3 |
0ug~2000ug/m³ |
±25% |
|
PM2.5 |
1ug/m3 |
0ug/m3~999ug/m³ |
±10% |
|
PM10 |
1ug/m3 |
0ug/m3~1000ug/m³ |
±10% |
|
temperature |
0.1℃ |
-20℃~60℃ |
±0.5℃ |
|
humidity |
0.1%RH |
5~95%RH |
±5%RH |
|
connecting terminal |
Communication: RJ45 interface, power supply: DC power port |
|
output signal |
RS485 |
|
working voltage |
5.0±0.2VDC |
|
Average working current |
≤80mA |
|
Warm-up time |
2 minutes (formaldehyde and TVOC need to be preheated and stabilized, other parameters will be displayed upon power on) |
|
operation temperature |
0℃~50℃ |
|
Working humidity |
≤95%RH |
|
External dimensions |
Diameter 168mm, height 51mm |
|
service life |
3 years |
|
interface |
name |
function |
|
1 |
RJ45 port 6th pin |
RS485A |
|
2 |
RJ45 port pin 8 |
RS485B |
|
3 |
Power hole |
Connect to a 5VDC power supply |

Preheat for at least 2 minutes before initial power on use
Do not expose this module to high concentrations of organic gases and corrosive gases for extended periods of time
Do not install the module in a strongly convective gas environment for use
To avoid contamination by large dust particles or even flocculent substances such as ground dust, floating debris, etc., which may cause fan entanglement and stall, build
Appropriate pre filtering treatment should be adopted for the use of equipment
Users should not disassemble the sensor, including the metal shielding shell, to prevent irreversible damage
This sensor is suitable for ordinary indoor environments
1. Overview of RS485 Communication Protocol
The communication protocol provides a detailed description of the input and output commands, information, and data of the seven in one air quality detector for third-party use and development.
Physical interface:
Connect the main communication port of the upper computer using a standard serial RS-485 communication port.
The information transmission method is asynchronous, with a start bit of 1, a data bit of 8, a stop bit of 1, and no checksum. The default data transmission rate is 9600b/s
2. Communication protocol details
2.1 Communication Method
1) All loop communication should follow the master/slave mode. In this way, information and data are transmitted between a single master station and a slave station (monitoring device).
2) Supports broadcast mode.
3) Under no circumstances can communication start from a slave station.
4) If the master station or any slave station receives a package containing an unknown command, the package will be ignored and the receiving station will not respond.
2.2 Return data frame structure description
Each data frame is composed of the following: (RTU mode)
address
function code
data quantity
Data 1
...
Data n
CRC 16 bit checksum
3. Transmission format
1) Host sends read address command:
|
address |
function code |
Register Address High Bit |
Low bit register address |
High number of data bits |
Low number of data points |
CRC 16 bit verification |
|
00 |
03 |
01 |
00 |
00 |
01 |
Xxxx is low in the front |
Return address from machine:
|
address |
function code |
byte length |
Address high bit |
Low order address |
CRC 16 bit verification |
|
00 |
03 |
02 |
00 |
xx |
Xxxx is low in the front |
Example: Sent: 00 03 01 00 00 01 84 27
Response: 00 03 02 00 addr CRCL CRCH If addr=2, the sensor address read is 2
2) Host sends read data command:
|
address |
function code |
High bit of data starting address |
Low order starting address of data |
Return the high digit of the number of data |
Return the low order of the number of data |
CRC 16 bit verification |
|
xx |
03 |
00 |
02 |
00 |
07 |
Little Endian |
At present, it only supports reading all data, starting from address 0002 and reading 7 data values. There are only 7 sensor data, corresponding to 7 sensor addresses. The high bit of the starting address of the data is always 0, and the high bit of the returned data is always 0
Internal message information
|
start address |
Number of data |
describe |
|
It can only be as follows: |
|
|
|
0x0002 |
1 |
CO2 concentration |
|
0x0004 |
1 |
Formaldehyde concentration |
|
0x0006 |
1 |
TVOC concentration |
|
0x0008 |
1 |
PM2.5 concentration |
|
0x000A |
1 |
PM10 concentration |
|
0x000C |
1 |
Temperature value |
|
0x000E |
1 |
Humidity value |
The starting address can only use addresses from the above list, otherwise there will be no response If the number of data exceeds, there will be no response. For example, if the starting address is 0X000C, the number of data that can be returned can only be 1 or 2. If 3 data are to be returned, there will be no response Similarly, for address 0X000E, the number of returned data can only be 1. If the number of returned data is 0, there will be no response.
Return value from slave sensor:
|
Slave address |
function code |
Number of data |
Data N |
CRC |
|
XX |
03 |
xx |
xx |
xxxx |
Byte length only refers to the length of data.
|
N0 |
N1 |
N2 |
N3 |
N4 |
N5 |
N6 |
N7 |
N8 |
N9 |
N10 |
N11 |
N12 |
N13 |
|
CO2 high level |
Low CO2 level |
Formaldehyde high level |
Low level formaldehyde |
TVOC high position |
TVOC low level |
PM2.5 high level |
PM2.5 low level |
PM10 high level |
PM10 low level |
High temperature |
Low temperature |
High humidity level |
Low humidity level |
Example: Host sends 01 03 00 02 00 07 CRCL CRCH
Response: 01 03 0E 02 26 00 26 00 34 00 0E 00 11 01 1C 02 5D CRCL CRCH