Intelligent pressure transmitterOverview
Adopting an integrated junction box design, it has wiring terminals and pointer or LCD digital display, making installation, inspection, and maintenance convenient. Selected imported original isolation membrane pressure sensors and integrated circuits ensure excellent performance of the product, similar to the 2088 from ROSEMUNT in the United States, making it an ideal diffusion silicon industrial pressure measurement and control instrument.
Main technical performance:
Measurement range: -0.1... 0~0.01... 100MPa
Overload: 1.5 times full range pressure
Pressure type: gauge pressure or absolute pressure or sealed reference pressure
Accuracy: Typical: ± 0.25% FS; Maximum: ± 0.5% FS;
(including nonlinearity, hysteresis, and repeatability)
Long term stability: typical: ± 0.1% FS; maximum: ± 0.2% FS;
Zero temperature drift: 0.03% FS/℃ (≤ 100KPa); 0.02%FS/℃(>100KPa);
Full temperature drift: 0.03% FS/℃ (≤ 100KPa); 0.02%FS/℃(>100KPa);
Working temperature: ordinary type: -30~80 ℃
Storage temperature: -40~120 ℃
Power supply: 15-28VDC
Output signal: 4-20mADC
Transmission method: Two line
Load resistance: ≤ (u-12)/0.02 Ω
Process connection: M20 × 1.5 external thread
Or G1/2 external thread with sealing gasket (flush diaphragm)
Shell protection: 1P65
Electrical Connection: Terminal Blocks
Overall dimensions




Intelligent pressure transmitterInstallation method
In general, transmitters should be installed vertically upwards from the horizontal direction. If limited by environmental conditions, the transmitter is allowed to be installed with a maximum tilt of 30 degrees from the horizontal direction.
It is not allowed to install the transmitter upside down.
It is strictly prohibited to dismantle, drop, or forcefully twist wires, and it is strictly prohibited to poke pressure holes with hard objects such as iron wires or steel needles. It can be directly installed on the flange joint of the measuring pipeline. For the convenience of installation and maintenance, a shut-off valve should be installed between the flange joint and the pipeline.
5、 Electrical connection
When wiring, the various terminal definitions specified in the following diagram should be followed, and the following methods should be used for connection.
Unscrew the side cover of the wiring terminal and connect the wires according to the diagram.