E-mail
2484289854@qq.com
-
Phone
18030056903
-
Address
Yudian Technology Building, No.17 Huoju North Road, Huoju High tech Zone, Xiamen City, Fujian Province
Xiamen Yudian Automation Technology Co., Ltd
2484289854@qq.com
18030056903
Yudian Technology Building, No.17 Huoju North Road, Huoju High tech Zone, Xiamen City, Fujian Province
AI-86X8 series universal multi circuit temperature controllerIntroduction
It is an 8-circuit regulator with multiple functions and the ability to externally expand multiple input and output modules. By adding external expansion modules, AI-8x88 can achieve up to 96 measurement and control functions, meeting the needs of various emerging industries for small volume and multi loop control. In the extended mode, the upper computer only needs to communicate with one instrument to control up to 96 measurement and control circuits, which can greatly improve communication efficiency compared to the mode that requires accessing multiple address instruments. Its commonly used parameters allow unlimited number of writes from the upper computer, and the internal memory of the instrument will not be damaged due to frequent writes from the upper computer. The parameter write restriction function only allows modification of specific or all instrument parameters when Loc is set to a specific value, which can reduce the occurrence of communication software writing errors leading to abnormal instrument operation.
AI-86X8 series universal multi circuit temperature controllerFeatures:
1. Multi loop intelligent temperature controller, compatible with multiple PT100 and PT1000 input specifications, with a measurement accuracy of 0.15 level;
2. Use one 24 bit high-performance AD converter for sampling every 4 channels, with a minimum sampling speed and control cycle of 0.5 seconds;
3. Optional NPN, PNP, and SSR driver outputs or linear voltage/current outputs, and optional 2-channel alarm outputs;
4. Single machine supports Modbus communication protocol, and if combined, it can also support communication methods such as TCP, EtherCAT, and DeviceNET.
Technical indicators
● Communication method: Bottom RS485 bus terminal; Support MODBUS-RTU protocol; The baud rate is adjustable from 4800 to 115200; The bottom RS485 bus terminal can be connected to our TCP-MODBUS and EtherCAT communication controllers, supporting relevant communication protocols; The internal dedicated communication protocol is used between the host, slave, and expansion module, with a reliable communication distance of 30m. Communication delay: When connected in series, each input or output expansion module node has a communication delay of about 10mS (including data transmission time);
● Input specifications: Thermistors: Cu50, Pt100, Ni120, Pt1000, etc. External expansion input modules: see related expansion input modules for performance
Measurement range: Cu50 (-50~+150 ℃), Pt100 (-200~+800 ℃), Pt100 (-200.00~+300.00 ℃), Pt1000 (-200.00~+300.00 ℃) Linear input: -9990~+32000 to be defined by the user
Measurement accuracy: 0.15~0.2 level
Measurement of temperature drift: ≤ 75PPM/℃
● Control cycle: minimum 20ms (single loop control); When there are multiple circuits, each circuit occupies 10ms of time;
Adjustment method: positional adjustment method (adjustable backlash); AI artificial intelligence regulation, including advanced control algorithms with fuzzy logic PID regulation and parameter self-tuning functions; Manual control mode;
Output specifications (modular): Linear current output: 0~20mA; 4~20mA, resolution of about 20000 words, maximum load of 260 ohms (energy-saving type); Linear voltage output: 1-5V; 0-10V, etc., with a resolution of approximately 10000-20000 words; SSR driver output: 5VDC/30mA (energy-saving type) or 12VDC/30mA; NPN or PNP switch output: maximum voltage 28V, maximum current 100mA. When driving the relay coil, a fast recovery diode must be connected in parallel with the relay coil to absorb the reverse voltage;
● Alarm function: upper limit, lower limit, deviation upper limit, deviation lower limit and other methods
Electromagnetic compatibility: IEC61000-4-4 (electrical fast transient pulse group) ± 6KV/5KHz, IEC61000-4-5 (surge) 6KV, and under 10V/m high-frequency electromagnetic field interference, the instrument does not crash or I/O port misoperation, and the measurement value fluctuation does not exceed ± 5% of the range
● Isolation and voltage resistance: The power supply terminal, relay contacts, and signal terminals are ≥ 2300V between each other; the weak current signal terminals that are isolated from each other are ≥ 600V between each other
Power supply: 24VDC, -15%,+10%
Power consumption: ≤ 0.3W (without any output or external feeding energy consumption); The maximum power consumption of the whole machine is ≤ 3W
● Operating environment: Temperature -10~60 ℃; Humidity ≤ 90% RH