AI-6516GJ1 high-voltage fully isolated temperature acquisition moduleIntroduction:
Supports up to 16 thermocouple isolation inputs, with one option for alarm. This machine is a pure measuring instrument and can be used as an input expansion module when control is required. It can also be connected to an external control table
Features:
1. Supports input specifications for 16 high-voltage fully isolated thermocouples;
2. Equipped with 2 sets of A/D inspection sampling to achieve high-speed data acquisition and processing;
3. Only supports temperature measurement, with a measurement accuracy of 0.2 level.
AI-6516GJ1 high-voltage fully isolated temperature acquisition moduleTechnical Specifications
● Communication method:
Bottom RS485 bus terminal; Support MODBUS-RTU protocol; The baud rate is adjustable from 2400 to 115200;
The bottom RS485 bus terminal can be connected to our TCP-MODBUS and EtherCAT communication controllers, supporting relevant communication protocols;
The internal dedicated communication protocol is used between the host, slave, and expansion module, with a reliable communication distance of 30m
Communication delay: When connected in series, the communication delay of each input or output expansion module node is about 10ms (including data transmission time);
● Input specifications:
Thermocouples: K, S, R, E, J, T, B, N, WRe3-WRe25, WRe5-WRe26, etc
Linear voltage: 0~75mV, 0~20mV, 0~50mV, etc
Measurement range: K (-200~+1300 ℃), S (-50~+1700 ℃), R (-50~+1700 ℃), T (-200~+350 ℃), E (0~800 ℃), J (0~1000 ℃), B (200~1800 ℃), N (0~1300 ℃), WRe3-WRe25 (0~2300 ℃), WRe5-WRe26 (0~2300 ℃)
Linear input: -9990~+32000 defined by the user
Measurement accuracy: AI-6516G (0.2 level);
Measurement of temperature drift: ≤ 100PPM/℃
● Control cycle: minimum 600ms;
● Alarm function: upper limit, lower limit, deviation upper limit, deviation lower limit and other methods
Electromagnetic compatibility: IEC61000-4-4 (electrical fast transient pulse group) ± 6KV/5KHz, IEC61000-4-5 (surge) 6KV, and under 10V/m high-frequency electromagnetic field interference, the instrument does not crash or I/O port misoperation, and the measurement value fluctuation does not exceed ± 5% of the range
Isolation and voltage resistance: Input signals must be at least 200V between each other
Power supply: 24VDC, -15%,+10%
Power consumption: ≤ 0.3W (without any output or external feeding energy consumption); The maximum power consumption of the whole machine is ≤ 3W
● Operating environment: Temperature -10~60 ℃; Humidity ≤ 90% RH