Overview of Electromagnetic Valve 1
Due to its structural form and working principle, solenoid valves are significantly different from other valves. They have clear requirements for the type of medium used, temperature, working pressure, and especially pressure difference, resulting in more precise coordination of internal components of solenoid valves. Therefore, the characteristics of solenoid valve failure are also significantly different from other working valves.
Main causes and troubleshooting methods of 2 solenoid valves:
fault |
Root cause analysis |
exclusion method |
Can't open |
The normally closed solenoid valve has a power failure or excessive fluctuation when connected to the power supply |
Check and eliminate power supply faults |
The working voltage of the electromagnetic drive device for normally closed solenoid valves does not match the actual voltage |
Replace the electromagnetic drive device with consistent voltage |
|
Actual work pressure exceeds the pressure determined in the contract |
Replace the solenoid valve with one that matches the actual working pressure |
|
The viscosity of the actual working medium is too high |
Choose other valves |
|
The actual working medium temperature exceeds the contractually determined value |
Replace the solenoid valve with a temperature consistent with the actual working medium |
|
Electromagnetic device damaged |
Repair or replace |
|
Electromagnetic device controller (box) malfunction |
Repair or replace |
|
The valve internals are stuck by foreign objects |
Clean the valve internals |
|
Damaged auxiliary valve cup or blocked pilot hole |
Repair or replace the auxiliary valve cup, clean the pilot hole |
|
Failure to activate auxiliary spring |
replace the spring |
|
Excessive wear of valve cup and cylinder liner leads to excessive clearance |
Replace the valve cup or cylinder liner |
|
I can't turn it off |
The normally open solenoid valve has a power failure or excessive fluctuation when connected to the power supply |
Check and eliminate power supply faults |
The working voltage of the electromagnetic drive device for normally open solenoid valves does not match the actual voltage |
Replace the electromagnetic drive device with consistent voltage |
|
Actual work pressure exceeds the pressure determined in the contract |
Replace the solenoid valve with one that matches the actual working pressure |
|
The viscosity of the actual working medium is too high |
Choose other valves |
|
The actual working medium temperature exceeds the contractually determined value |
Replace the solenoid valve with a temperature consistent with the actual working medium |
|
Electromagnetic device damaged |
Repair or replace |
|
Electromagnetic device controller (box) malfunction |
Repair or replace |
|
There are foreign objects in the gap between the valve components |
Clean the valve internals |
|
Damaged valve cup seal or diaphragm |
Replace the seal or diaphragm |
|
Close auxiliary spring failure |
replace the spring |
|
Installation direction incorrect |
Install in the direction indicated by the valve body flow direction |
|
The medium has repeated bidirectional pressure |
Select bidirectional solenoid valve |
|
abnormal noise |
There are foreign objects inside the valve |
Clean the valve internals |
The driving iron core cannot be * attracted |
Repair and adjust |
|
Low traffic |
Insufficient valve cup travel |
readjust |
Insufficient suction of electromagnetic device |
readjust |
|
Insufficient pressure difference, main valve cup cannot be opened * |
Select direct acting solenoid valve |
3 Conclusion
The occurrence of solenoid valve failure is mainly due to unclear description of operating conditions, inconsistent working pressure difference with reality, or inconsistent temperature. Therefore, accurate selection and troubleshooting are crucial for the use of solenoid valves. Shanghai Mingjing Anti corrosion Valve Manufacturing Co., Ltd. is a professional manufacturer engaged in the research and production of solenoid valves, which can provide detailed consultation and selection solutions for users.
Shanghai Mingjing Anti corrosion Valve Manufacturing Co., Ltd
Technical Department