Measurement principle:
Used for measuring liquid media. Piezoelectric drive is the core of VEGASWING, and the vibrating element (tuning fork) vibrates at a certain mechanical resonance frequency under the drive of piezoelectric ceramics. When in contact with a medium, the vibration frequency of the tuning fork will decrease. The integrated electronic component detects changes in vibration frequency and converts them into switch commands. Piezoelectric ceramics are mechanically fixed, very stable and durable. The length * of tuning fork can be as short as 40mm. Pressure, temperature, foam and bubbles, and even viscosity will not affect the switching accuracy. Due to the rated width being only DN25, there is no problem with pipeline installation.
■ Advantages:
-Almost unaffected by the characteristics of the medium.
-The medium temperature ranges from -50 ° C to 250 ° C.
-The working environment pressure ranges from -100kPa to 6400kPa.
-Installation and maintenance are both very simple.
■ Application:
Limit detection of liquid media is commonly used in overflow or idle protection systems.
Main performance parameters:
-SIL2 certification;
-Easy installation and startup, no need for specialized debugging;
-Piezoelectric driven ceramics with fixed threads;
-Very high reliability;
-The switch point is not affected by the medium;
-Wear resistant and maintenance free;
-Belonging to Plics ® Product series.
■ Selection Guide
| Security certification: | ||||||||
| XX | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | No explosion-proof requirements | |
| XA | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | Overflow protection (WHG standard) | |
| CA | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | ATEX II 1G, 1/2G, 2G Ex ia IIC T6 + WHG | |
| DA | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | ATEX II 1/2G, Ex d IIC T2...T6 + WHG | |
| CM | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | ATEX II 1G, 1/2G, 2G Ex ia IIC T6+Marine License | |
| DM | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | ATEX II 1/2G, Ex d IIC T2... T6+Marine License | |
| CI | IECEx Ex ia IIC T6 | |||||||
| DI | IEC Ex Ex d IIC T6...T2 Ga/Gb | |||||||
| GI | IECEx Ex tD A20/21 IP66 T, A21 | |||||||
| XM | ┄ | ┄ | ┄ | ┄ | ┄ | ┄ | Marine license | |
| │ | Installation connection/materials: | |||||||
| │ | GBV | ┄ | ┄ | ┄ | ┄ | ┄ | Thread G three-quarters (DIN 3852-A) PN64/316L | |
| │ | NBV | ┄ | ┄ | ┄ | ┄ | ┄ | Thread: NPT (ASME B1.20.1) PN64/316L | |
| │ | GAV | ┄ | ┄ | ┄ | ┄ | ┄ | Thread G1 (DIN 3852-A) PN64/316L | |
| │ | NAV | ┄ | ┄ | ┄ | ┄ | ┄ | Thread 1NPT (ASME B1.20.1) PN64/316L | |
| │ | CCN | ┄ | ┄ | ┄ | ┄ | ┄ | Clamp 1 "PN16 (ø 50.5mm) DIN32676, ISO2852/316L Ra<0.3 μ m | |
| │ | CCP | ┄ | ┄ | ┄ | ┄ | ┄ | Clamp 1 "PN16 (ø 50.5mm) DIN32676, ISO2852/316L Ra<0.8 μ m | |
| │ | CAN | ┄ | ┄ | ┄ | ┄ | ┄ | Clamp 2 "PN16 (ø 64mm) DIN32676, ISO2852/316L Ra<0.3 μ m | |
| │ | CAP | ┄ | ┄ | ┄ | ┄ | ┄ | Clamp 2 "PN16 (ø 64mm) DIN32676, ISO2852/316L Ra<0.8 μ m | |
| │ | RAN | ┄ | ┄ | ┄ | ┄ | ┄ | Bolt DN40PN40 DIN11851/316L Ra<0.3 μ m | |
| │ | RAP | ┄ | ┄ | ┄ | ┄ | ┄ | Bolt DN40PN40 DIN11851/316L Ra<0.8 μ m | |
| │ | FPV | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN25PN40 Form C, DIN 2501/316L | |
| │ | FPH | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN25PN40 Form C, DIN 2501/ECTFE | |
| │ | FEV | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN50PN40 Form C, DIN 2501/316L | |
| │ | FEH | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN50PN40 Form C, DIN 2501/ECTFE | |
| │ | FEF | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN50PN40 Form C, DIN 2501/PFA | |
| │ | FPS | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN25PN40 Form B1, EN 1092-1/Enamel | |
| │ | FES | ┄ | ┄ | ┄ | ┄ | ┄ | Flange DN50PN40 Form B1, EN 1092-1/Enamel | |
| │ | APV | ┄ | ┄ | ┄ | ┄ | ┄ | Flange 1 "150lb RF, ANSI B16.5/316L | |
| │ | APH | ┄ | ┄ | ┄ | ┄ | ┄ | Flange 1 "150lb RF, ANSI B16.5/ECTFE | |
| │ | APE | ┄ | ┄ | ┄ | ┄ | ┄ | Flange 1 "150lb RF, ANSI B16.5/enamel | |
| │ | ACV | ┄ | ┄ | ┄ | ┄ | ┄ | Flange 2 "150lb RF, ANSI B16.5/316L | |
| │ | ACH | ┄ | ┄ | ┄ | ┄ | ┄ | Flange 2 "150lb RF, ANSI B16.5/ECTFE | |
| │ | ACE | ┄ | ┄ | ┄ | ┄ | ┄ | Flange 2 "150lb RF, ANSI B16.5/enamel | |
| │ | │ | Adapter/Operating Temperature: | ||||||
| │ | │ | X | ┄ | ┄ | ┄ | ┄ | None/-50~150 ° C | |
| │ | │ | T | ┄ | ┄ | ┄ | ┄ | Yes/-50~250 ° C | |
| │ | │ | G | ┄ | ┄ | ┄ | ┄ | Airtight execution/-50~150 ° C | |
| │ | │ | D | ┄ | ┄ | ┄ | ┄ | Airtight execution/-50~250 ° C | |
| │ | │ | │ | Shell/Cable Entrance: | |||||
| │ | │ | │ | P | ┄ | ┄ | ┄ | Plastic casing/IP66/IP67/M20x1.5 | |
| │ | │ | │ | M | ┄ | ┄ | ┄ | Aluminum shell/IP66/IP67/M20x1.5 | |
| │ | │ | │ | U | ┄ | ┄ | ┄ | Aluminum casing IP66/IP67/Half NPT | |
| │ | │ | │ | 8 | ┄ | ┄ | ┄ | StSt (electrolytic polishing) 316L/IP66/IP67/M20x1.5 | |
| │ | │ | │ | │ | Output interface: | ||||
| │ | │ | │ | │ | C | ┄ | ┄ | Non contact electronic switch 20... 250VAC/DC | |
| │ | │ | │ | │ | R | ┄ | ┄ | DPDT relay 20... 72VDC/20... 250VAC (3A) | |
| │ | │ | │ | │ | T | ┄ | ┄ | Transistor output (NPN/PNP) 10... 55VDC | |
| │ | │ | │ | │ | Z | ┄ | ┄ | Two line output 8/16 mA 12... 36VDC | |
| │ | │ | │ | │ | N | ┄ | ┄ | NAMUR signal output | |
| │ | │ | │ | │ | │ | Switching point: | |||
| │ | │ | │ | │ | │ | X | ┄ | standard | |
| │ | │ | │ | │ | │ | L | ┄ | Same as SWING81 or 81A | |
| ↓ | ↓ | ↓ | ↓ | ↓ | ↓ | |||
| SWING61. | ## | ### | # | # | # | # | : Select model |