Easy to install residual current transformers can be used in conjunction with ARCM series electrical fire monitoring devices, ARD series motor protection devices, and ASJ series residual current relays. This product has the characteristics of easy installation and compact size.
Product Details

Easy to install residual current transformersProduct Features

Electrical fire residual current transformer, used for collecting low-voltage residual current signals, can be used in conjunction with ARCM series electrical fire monitoring devices, ARD series motor protection devices, and ASJ series residual current relays. This product has the characteristics of easy installation and compact size.

Usage environment

Rated working voltage AC 0.66kV (maximum AC 1.14kV)

Rated frequency 50-60Hz

Environmental temperature -30 ℃~70 ℃

Altitude ≤ 3000m

Power frequency withstand voltage 3000V/1min 50Hz

Used in places where there is no direct rain or snow invasion, no serious pollution, and no severe vibration

Specification and size, residual current transformer for electrical fire

AKH-0.66 LXXC external dimensions:

便于安装剩余电流互感器便于安装剩余电流互感器



Easy to install residual current transformersInstallation and commissioning precautions
  1. Installation location

    • Avoid interferenceKeep away from strong magnetic field sources (such as transformers and reactors) and power cables (recommended spacing ≥ 50cm).

    • vertical installationEnsure that the axis of the transformer is perpendicular to the wire to reduce measurement errors.

    • securely fixedUse buckles or bolts for fastening to prevent poor contact caused by vibration.

  2. Wiring specifications

    • Secondary side open circuit protectionIt is strictly prohibited to operate in an open circuit on the secondary side of the transformer, otherwise it may generate high voltage and endanger personal safety.

    • Shielded wire groundingThe analog output signal line needs to use shielded twisted pair cables, and the shielding layer should be grounded at one end (usually grounded at the receiving end).

    • Polarity correctDigital output requires confirmation of communication line A/B polarity to avoid communication failure.

  3. Debugging steps

    • zero point calibrationAdjust the zero offset of the transformer when there is no residual current (some products support automatic calibration).

    • Range verificationInject a known residual current (such as 100mA) using a standard source and check if the output signal is accurate.

    • Alarm threshold settingAccording to regulatory requirements (such as the residual current alarm value for building electrical systems usually being 300mA), set the operating value of the protective device.