E-mail
20460015@qq.com
-
Phone
13587713660
-
Address
Xiyanggang Industrial Zone, Gulin Town, Haishu District, Ningbo City
Ningbo Qixuan Da Technology Co., Ltd
20460015@qq.com
13587713660
Xiyanggang Industrial Zone, Gulin Town, Haishu District, Ningbo City
Product Overview:
PMC-530Asmart electricity meterIt is designed based on the technology of digesting similar imported products from abroad and in accordance with China's requirements for the operation of power equipment and computer intelligent monitoring. This product is a comprehensive electricity monitoring instrument that integrates ammeters, voltmeters, power meters, power factor meters, and kilowatt hour meters. The RS485 communication interface connects the instrument to the computer network of the monitoring center, making it a high-performance automation instrument suitable for modern power supply and distribution systems such as industrial and mining enterprises, civil buildings, and building automation in China.
Comprehensive collection of power parameters for 50/60Hz power supply systems using power meters; Measure and display three-phase voltage, three-phase current, active power, reactive power, power factor, frequency, active energy (cumulative), and reactive energy (cumulative). The value of electrical energy is only used for internal secondary measurement assessment and accounting purposes within the enterprise, and is not used for pricing, measurement, or payment purposes
Standard configuration:
⑴Instruments measure high/low voltage three-phase current, three-phase voltage, active power, reactive power, power factor, frequency, active energy, and reactive energy on the power grid.
⑵Standard CT, PT or voltage signals are directly input.
⑶Wide range AC/DC80-265V or AC 220V universal power supply.
⑷The display adopts two specifications of LCD and LED with wide viewing angle and white backlight, and all instrument parameters can be set through the display panel buttons.
⑸Equipped with RS-485 communication interface (optical isolation) and ModBus RTU communication protocol
⑹Adopting a disc opening installation method (LCD sizes are only available in 120 * 120 and 96 * 96)
Dimensions: 120 * 120mm, 96 * 96mm, 80 * 80mm, 72 * 72mm
Hole size: 112 * 112mm, 91 * 91mm, 76 * 76mm, 67 * 67mm
Technical indicators:
| Performance | Parameters | ||
| lose
enter
measure
quantity
apparent
show | Network | Three phase three wire, three phase four wire | |
| Voltage | rated value | AC100V、 400V (please specify when ordering) | |
| overload | Measurement: 1.2 times instantaneous: 2 times/10s | ||
| Power consumption | <1VA (Each phase) | ||
| Impedance | >300kΩ | ||
| Accuracy | RMSMeasurement, accuracy level 0.5% | ||
| electric current | rated value | AC1A、 5A (please specify when placing an order) | |
| overload | Duration: 1.2 times Instantaneous: 10 times/10 seconds | ||
| Power consumption | <0.4VA (Each phase) | ||
| Impedance | <20mΩ | ||
| Accuracy | RMSMeasurement, accuracy level 0.5% | ||
| Frequency | 40~60HZAccuracy of 0.1Hz | ||
| Power | Active, reactive, and real power, with an accuracy of 0.5% | ||
| Display | Programmable settings, switching, looping, display in both LCD and LED specifications | ||
| electricity metering | 4Quadrant electric energy | Four quadrant forward and reverse metering with active power accuracy of 0.5 level and reactive power of 2 level | |
| Large demand | Slip type, slip time of 1 minute, slip interval of 15 minutes | ||
| electricity source | scope of work | AC、DC 80V~265V | |
| Power consumption | ≤5VA | ||
| lose go out can compile, edit, weave, organize Cheng | Digital interface | RS-485、 MODBUS-RTU protocol | |
| pulse output | 2Pulse output of road electrical energy | ||
| Environment | working environment | -10~55℃ | |
| storage environment | -20~70℃ | ||
| Security | Voltage resistance | Auxiliary power supply, input signal, output signal>1.5kV | |
| Insulation | Input, output, and power supply to the chassis>5M | ||
| Appearance | Size | 120×120 96 X 96 80X80 72X72(Length, Width) | |
| Weight | 0.6kg | ||
wiring method

Example of ordering:
Example 1:PMC-530Asmart electricity meter
Signal input: AC380V (input voltage) 100/5A (current ratio)
Wiring method: three-phase four wire
Working power supply: AC220V or AC/DC80-265V
Other: (Unless otherwise specified, follow the default factory settings)
Example 2: Power meters
Signal input: AC10/0.1KV (input voltage) 100/5A (current ratio)
Wiring method: three-phase three wire
Working power supply: AC220V or AC/DC80-265V
Other: (Unless otherwise specified, follow the default factory settings)