Intelligent distribution transformer terminal

NegotiableUpdate on 07/03
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Intelligent distribution transformer terminal

Product Details

智能配变终端.jpg

summary:
The SCPB-615B intelligent distribution transformer terminal is designed in accordance with Q/GDW614-2011 "Functional Specification and Technical Conditions for Intelligent Low Voltage Distribution Box in Rural Power Grid", Q/GDW615-2011 "Functional Specification and Technical Conditions for Intelligent Distribution Transformer Terminal in Rural Power Grid", and DL/T 721-2013 "Remote Terminal of Distribution Network Automation System" standards, fully meeting the standard requirements and achieving partial expansion functions. It has passed the formal tests required by relevant standards.

Product features:
1. The core processor is based on the ARM-A7 platform, and the sub modules are implemented by microcontrollers, forming a master-slave multi CPU system with module plug-in design.
2. Embedded Linux operating system, combined with SQLite database, hierarchical and distributed software design, stable system operation, flexible function expansion, and simple and convenient maintenance.
3. Green, environmentally friendly, low-carbon and energy-saving design, with a total power consumption of less than 8VA, significantly better than the standard requirements.
4. The terminal integrates a supercapacitor as a backup power supply, which can maintain the normal operation of the terminal and terminal communication module for at least 1 minute.
5. Users can choose the reactive power compensation function module, which has three compensation functions: separate compensation, joint compensation, and phase to phase compensation.
6. Adopting low-power wireless and broadband carrier communication methods to achieve the function of three-phase imbalance control.

Main functions:
-Detection and protection of distribution transformers
Statistical data on voltage, current, active and reactive power, power factor, phase failure, harmonics, power quality, environmental temperature, etc. It has multiple protection and warning functions such as overvoltage, overcurrent, overload, undervoltage, overheating, etc.
-Electric energy information collection
Collect electrical energy information in the substation area, monitor and report the operating conditions of the substation metering table.
-Remote control and load management
By controlling commands through the main station, remote management of circuit breaker opening and closing can be achieved; The main station can issue various load management measures to the terminal.
-Reactive power compensation control
Fast dynamic compensation of reactive power in the distribution station area and monitoring of capacitor switching status
-Three phase unbalance control
By monitoring the three-phase imbalance situation in the substation area, intelligent switches or other three-phase imbalance adjustment devices connected can be controlled to adjust the three-phase imbalance.
-Outgoing current collection and distributed power generation
Collect the outgoing current of distribution transformers and monitor it in real-time for external distributed power sources.
-Event record query and reporting
Automatically record, upload, and recall alarm events that occur in the distribution station area.
-Plug and play automatic configuration
The terminal has the ability to self describe information in accordance with IEC61850 and can achieve plug and play functionality in the main station system.

Technical parameters:

Working power supply
AC220V/380V±30%,50Hz
Analog quantity acquisition Transformer module 3 voltage channels, 3 current channels
Non electric analog input DC analog input 2 PT100 channels, 2 reserved channels
State input Remote signal quantity Route 16
control output Relay Route 10
Reactive power compensation Route 12
communication interface RS485 3 routes
RS232 2 routes
Ethernet 2 routes
2G/3G/4G wireless public network 1 Road
USB 1 Road
Broadband Carrier 1 Road
Micro power wireless 1 Road
communication protocol Network-Layer Protocol IPv4,IPv6
application layer protocol Modbus,DL/T645,Q/GDW1376.1,Q/GDW1376.4,DL/T634.5101,DL/T634.5104
environmental condition ambient temperature -45 ℃ to 70 ℃
relative humidity 10%-100%
Maximum absolute humidity 35g/m³
altitude Not exceeding 1000m
Terminal size Dimensions (width * height * depth) 267mm*174mm*153mm
Installation dimensions (width * height) 310mm*110mm