GB14287.4-2014 Electrical Fire Monitoring System Part 4: Fault Arc Detection Device
Establish a database of civil building fault arcs and compile national standardsGB14287.4-2014 "Electrical Fire Monitoring System Part 4: Fault Arc Electrical Fire Monitoring Detector".
GB50116-2013 Design Specification for Automatic Fire Alarm System
9.2.4 Electrical fire monitoring detectors with circuit fault arc detection function should not have a protection circuit length greater than 100m.
12.4.6 Spaces with a height greater than 12 meters: Electrical fire monitoring detectors should be installed on electrical circuits, and electrical fire monitoring detectors with fault arc detection function should be installed on lighting circuits.
Fault arc commonly known asElectric spark "is a gas free discharge phenomenon caused by air breakdown due to insulation aging and damage, loose electrical connections, humid air, and sharp voltage and current increases in electrical circuits or equipment. Its main hazard is causing fires.
Due to the influence of time and working environment, cables may experience varying degrees of aging, resulting in various electrical circuit safety issues such as leakage, overload, and short circuit. Although circuit breakers and leakage fire monitoring products widely used in the market provide protection against line short circuits, overloads, or leakage faults. However, the dangerous arc sparks generated instantly by short-circuit fault points and electrical faults such as small current fault arcs that cannot be detected by ordinary circuit breakers still result in a high incidence of electrical fires every year.
Fault arc detectorHYFA has the following functions: