E-mail
13349227851@163.com
-
Phone
13349227851
-
Address
No. 7829, Mount Huangshan Avenue, Bengbu
Anhui Lijin Environmental Protection Technology Co., Ltd
13349227851@163.com
13349227851
No. 7829, Mount Huangshan Avenue, Bengbu
Here's a copy for youEngineering Common Version "Selection Table for Electrostatic Water Treatment Equipment" (Side Flow System)The model is universal and the parameters are compatible with air conditioning circulating water and industrial circulating water systems, which can be directly used for design, bidding, and quotation.
Note: There may be slight differences in the naming of models from different manufacturers. This table is for industry standard configurations and can be selected based on flow rate or pipe diameter.
| model | Processing flow rate (m ³/h) | Device interface diameter (DN) | Applicable mainstream volume of the system (m ³/h) | Applicable pipe diameter (main pipeline) |
|---|---|---|---|---|
| L-10 | 5–10 | DN25 | 80–150 | DN65–DN80 |
| L-20 | 10–20 | DN32 | 150–300 | DN80–DN100 |
| L-30 | 20–30 | DN40 | 300–450 | DN100–DN125 |
| L-50 | 30–50 | DN50 | 450–800 | DN125–DN150 |
| L-80 | 50–80 | DN65 | 800–1300 | DN150–DN200 |
| L-100 | 80–100 | DN80 | 1300–1800 | DN200–DN250 |
| L-150 | 100–150 | DN100 | 1800–2500 | DN250–DN300 |
| L-200 | 150–200 | DN125 | 2500–3500 | DN300–DN350 |
| L-300 | 200–300 | DN150 | 3500–5000 | DN350–DN400 |
| L-400 | 300–400 | DN200 | 5000–6500 | DN400–DN450 |
| L-500 | 400–500 | DN250 | 6500–8000 | DN450–DN500 |

| model | Mainstream processing flow rate (m ³/h) | Pipe diameter (DN) |
|---|---|---|
| L-20 | 10–20 | DN40 |
| L-40 | 20–40 | DN50 |
| L-80 | 40–80 | DN65 |
| L-100 | 80–100 | DN80 |
| L-150 | 100–150 | DN100 |
| L-200 | 150–200 | DN125 |
| L-300 | 200–300 | DN150 |
| L-400 | 300–400 | DN200 |
| L-500 | 400–500 | DN250 |
| L-800 | 500–800 | DN300 |
| L-1000 | 800–1000 | DN350 |
| project | parameter |
|---|---|
| working power supply | AC220V / 380V |
| Output high voltage | 5-20 kV (stable and adjustable) |
| The biggest work pressure | ≤1.6 MPa |
| Equipment material | 304 stainless steel/Q235 internal anti-corrosion |
| Operating Temperature | 0–95℃ |
| Installation Method | Sidestream water/Mainstream water |
| Electrode material | Titanium based platinum coating/stainless steel |
| Control method | Digital display/PLC automatic |
| function | Anti scaling, corrosion inhibition, descaling, sterilization, algae inhibition |

Example: Mainstream flow of cooling water system500 m³/h
Side flow selection:25–50 m³/h
Corresponding model: LJ-50(30-50 m³/h)
Last Article: Basic working principle of condensate water recovery device
Next Article: Principle of Cooling Tower Scale Absorption Basket